IEEE 1584 Arc Flash Calculator

IEEE 1584 Arc Flash Calculator

Estimate arcing current, incident energy, and arc-flash boundary from the same field data used in an IEEE 1584-style study: bolted fault current, voltage, gap, enclosure, electrode configuration, working distance, clearing time, and arcing-current adjustment.

Switchgear and MCC presets

📋IEEE 1584-style inputs

This tool uses an IEEE 1584-style approximation for screening and sensitivity checks. It is not the published IEEE 1584 equation set and must not be used as a final arc-flash label or energized-work authorization.

💡Study notes

Arcing current check: IEEE 1584 studies evaluate expected arcing current and reduced arcing current because protective devices can clear more slowly at lower current.
Safety caveat: Use a qualified person, current one-line data, device curves, equipment dimensions, and the adopted edition of IEEE 1584/NFPA 70E before selecting PPE or labels.
208 V
Lower IEEE 1584 AC application limit
15 kV
Upper IEEE 1584 AC application limit
1.2
cal/cm² common arc-flash boundary basis
18-36
in typical working distance span
Adjusted arcing current
0.0
kA
Incident energy
0.0
cal/cm² at working distance
Arc-flash boundary
0
in to selected energy target
Energy class
Screen
compare with site PPE program

Calculation breakdown

Safety caveat: this result is a sensitivity estimate only. Final incident energy, arc-flash boundary, labels, PPE, and energized-work decisions require a qualified arc-flash study using the complete adopted IEEE 1584 method, accurate short-circuit data, protective-device clearing times at arcing current, and current NFPA 70E requirements.

🔌Electrode configuration comparison grid

VCB

Vertical conductors in a box. Common baseline for LV switchgear, panelboards, and MCC compartments.

VCBB

Vertical conductors terminated in an insulating barrier. Often raises calculated energy versus VCB.

HCB

Horizontal conductors in a box. Frequently severe for LV switchgear because plasma is directed outward.

VOA

Vertical conductors in open air. No enclosure focusing factor, but still requires a formal hazard analysis.

HOA

Horizontal conductors in open air. Directionality can increase exposure compared with vertical open air.

📊Reference tables

IEEE 1584-style inputCommon study valueWhy it mattersCheck before use
System voltage208 V to 15 kV ACAffects arcing-current behavior and applicable model rangeUse nominal equipment voltage at the bus
Bolted fault currentSite short-circuit kAStarting point for arcing current and device trip timeUse available current from a current study
Electrode gap25 mm LV MCC, 32 mm LV gear, 104 mm MV gearChanges arc voltage, current, and energy transferMeasure actual phase spacing where possible
Working distance18 in MCC, 24 in LV gear, 36 in MV gearIncident energy falls with distance from the arc sourceUse task-specific face and torso distance
Equipment classTypical voltageTypical gapTypical working distance
MCC bucket or starter section208-600 V25 mm18 in / 455 mm
Low-voltage switchboard208-600 V25-32 mm18-24 in / 455-610 mm
Low-voltage drawout switchgear480-600 V32 mm24 in / 610 mm
Medium-voltage metal-clad switchgear2.4-15 kV104-152 mm36 in / 915 mm
Incident energy levelCommon thresholdTypical meaningUse limitation
Arc-flash boundary basis1.2 cal/cm²Common onset of second-degree burn thresholdBoundary may be solved for another target
Arc-rated clothing category 14 cal/cm²Minimum arc rating for category 1 systemsDo not mix table method and study method
Arc-rated clothing category 28 cal/cm²Common daily arc-rated clothing thresholdUse employer PPE program requirements
High-energy range25-40 cal/cm²Category 3 and 4 comparison levelsRequires careful task and equipment review
ConfigurationApprox. energy tendencyTypical locationScreening note
VCBBaselinePanelboards, MCCs, LV switchgearOften default when conductors are vertical in box
VCBBHigher than VCBTerminations facing an insulating barrierBarrier can focus energy toward worker
HCBOften highest enclosed LV caseDrawout gear and bus compartmentsHorizontal conductors can project plasma outward
VOA / HOALower enclosure effectOpen-air conductors and outdoor structuresStill depends on task, geometry, and distance

An arc flash occur when energy is sudden released within the energized equipment, and the resulting arc flash can create burn hazard within milliseconds of the incident. Because an arc flash is such a serious hazard, many facility will perform arc flash studies to determine the degree of that hazard. As a result, many facilities employ tools based on the IEEE 1584 model that allow them to quickly perform arc flash checks in the equipment they operate.

The calculator included in this article will allow you to quickly perform arc flash checks for your facility. Bolted fault current is the available short-circuit current that can exit the terminal of the equipment. The current that arc between the equipment is always less than the bolted fault current, as the arc itself add resistance to the electrical circuit.

How to Use a Quick Arc Flash Calculator

However, the arcing current may cause the protective device of the equipment to take longer to clear the fault. As such, the adjustment field allow you to test the effect of the difference between the bolted fault current and the arcing current, a parameter that is difficultly to determine without formal arc flash studies. Voltage play a role in the arc flash because the physics of the arc flash are different at different voltage level.

As such, the IEEE 1584 model use different factors to calculate the energy of the arc flash at different voltage levels. For instance, arc flash are less stable at voltages under 300 volts. At higher voltages, more energy is directed into the arc flash.

Thus, the calculator account for voltage differences when calculating arc energy, such as between 480-volt motor control center and 4-kilovolt switchgear. Electrode configuration is another variable in arc energy; the way in which the conductor are arranged will affect the energy of the arc flash. For instance, vertical conductor within a box will behave differently than horizontal conductors within the same box.

Additionally, placing a barrier at the arc flash will alter the energy of the arc flash. These factor can be adjusted within the calculator to provide engineers with a view into how the energy of the arc flash will change due to these variables. The dimension of the enclosure in which the electrical equipment is installed will impact the energy of the arc flash.

Arc energy will be directed outward from a shallow and narrow enclosure, while some of the energy will dissipate before reaching the enclosure if the enclosure is deeper than narrow enclosure. These dimensions can be entered into the calculator to determine the impact that a deeper enclosure may have on arc energy. Working distance is another variable that engineers can be control, and is one of the most effective in reducing the risk of arc flash injury.

Moving an individual even six inch away from electrical equipment can significantly reduce the energy of the arc flash that reaches the human being. The reference table can provide engineers with the working distances for various type of electrical equipment, but the calculator can be used for any specific working distance for a task. Clearing time is the amount of time that a protective device take to clear a fault.

For example, if a relay take 80 milliseconds to clear a fault rather than the 200 milliseconds it would normally take, the energy of the arc flash will be almost half of the energy that would occur at that longer time. Because clearing time is one of the most critical parameter for electrical protection devices, most formal arc flash studies focus upon verifying trip curves for those device. Thus, the adjustment field within the calculator can be used to test different clearing time for the same equipment.

When you enter the parameters for your specific facility into the calculator, you will be able to determine the adjusted arcing current, the incident energy at the working distance, and the distance of the arc flash boundary. Each of these parameter will only provide engineers with a screening value to determine if the current fuses, working position, or enclosures of the electrical equipment will move the incident energy to a lower category of personal protection equipment (PPE) requirements. Thus, these screening value will help engineers determine whether the performance of a formal arc flash study is necessary at all locations.

The value of this quick arc flash calculation tool is that it ask engineers to gather important data about their facilities. For instance, a short circuit study of the power supply must determine the actual bolted fault current at each location. Additionally, the gap between the electrode at the equipment will need to be measured, as will the clearing time of the electrical device that supply that equipment.

These effort will uncover any gap in the documentation of electrical equipment within the engineers’ facilities. Finally, while this quick calculation tool is helpful for engineers in estimating the arc flash energy at different variables, it is not a replacement for the formal arc flash studies that must be completed at facilities with energy level near the thresholds for personal protection equipment (PPE). Instead, such an estimation tool can help engineers recognize when they should of hire a qualified engineer to complete a formal arc flash study that uses the complete IEEE 1584 equation and verified electrical device curve and drawings.

IEEE 1584 Arc Flash Calculator

Leave a Comment