Sub Panel Load Calculator

Sub Panel Load Calculator

Estimate subpanel demand from continuous and noncontinuous VA, convert the result to amperage, select the next standard feeder breaker, and compare headroom against the feeder and panel bus.

1Load presets
2Subpanel load inputs
Use the feeder voltage basis for the subpanel.
Marked subpanel bus or main-lug rating.
Breaker protecting the feeder conductors.
Loads expected to run three hours or more.
Intermittent receptacle, tool, or appliance VA.
Add EV, HVAC, lighting, rack, or process VA.
Add future branch circuits before demand factor.
Use 100% unless a valid load calculation supports diversity.
Check the inputs. Panel rating, feeder breaker, supply system, and demand factor must be positive, and demand factor cannot exceed 100%.
3Live load notes
Input statusEnter the subpanel load schedule to see demand load, feeder breaker size, and headroom.
Calculated load status Calculate to compare demand amps to the selected feeder breaker and panel bus rating.
Demand load 0 VA after 125% continuous and demand factor
Calculated amps 0 A on selected supply system
Minimum breaker 0 Next standard amp rating
Feeder headroom 0 A remaining on installed feeder
4Panel and load spec comparison grid
60 AFeeder

Calculate to compare installed feeder capacity against the adjusted load.

125%Continuous

Continuous loads are multiplied before adding demanded noncontinuous VA.

75%Demand

Demand factor is applied only to the noncontinuous load portion.

0 AHeadroom

Remaining amps appear after a valid load schedule is calculated.

5Standard feeder breaker reference
Standard breaker 120/240 V 1 phase capacity 208Y/120 V 3 phase capacity Typical subpanel use
30 A7,200 VA10,808 VASmall garage, shed, lighting, limited tools
40 A9,600 VA14,407 VAEquipment rack, light workshop, office circuits
50 A12,000 VA18,013 VABasement, detached room, small appliance mix
60 A14,400 VA21,611 VAWorkshop, garage expansion, mixed branch circuits
70 A16,800 VA25,216 VAStudio, larger garage, HVAC plus receptacles
80 A19,200 VA28,814 VAEV ready area, larger detached space
90 A21,600 VA32,419 VAKitchen remodel subpanel or dense branch circuits
100 A24,000 VA36,027 VASmall dwelling unit or high-capacity garage panel
125 A30,000 VA45,034 VALarge detached shop or three phase equipment panel
6Continuous and noncontinuous load examples
Load type Common VA basis Calculator bucket Formula treatment
Fixed lighting that stays onFixture schedule VAContinuous VAMultiply by 1.25 before adding to demand
Network rack or server gearNameplate watts or VAContinuous VAUse 125% if expected to run three hours or more
EV charger or process loadOutput amps x voltsContinuous VAUse continuous multiplier before breaker sizing
General receptacle circuitsLoad schedule VANoncontinuous VAApply selected demand factor if justified
Small shop toolsNameplate VA or circuit estimateNoncontinuous VAApply demand factor to intermittent load portion
Kitchen or laundry applianceNameplate VAUsually noncontinuousUse 100% unless the project load method permits demand
7Demand factor guide
Demand factor When it is conservative When to avoid it Calculator effect
100%Unknown mix or critical branch circuitsRarely too conservative for planningCounts all noncontinuous VA
90%Small panel with modest diversityLoads likely to run togetherRemoves 10% of noncontinuous VA
75%Garage or shop with intermittent toolsAppliance-heavy simultaneous loadsRemoves 25% of noncontinuous VA
60%Large mixed-use panel with documented diversityContinuous or life-safety load groupsRemoves 40% of noncontinuous VA
50%Concept planning only with strong diversity basisFinal feeder sizing without verificationHalves only the noncontinuous VA
8Panel load comparison table
Scenario Input load mix Adjusted demand Planning cue
Small garage 30 A1.2 kVA continuous, 3.6 kVA noncontinuous4.2 kVA at 75%Comfortable on a 30 A 120/240 V feeder
Equipment rack 40 A4.8 kVA continuous, 0.8 kVA noncontinuous6.6 kVA at 75%Continuous load dominates breaker size
Workshop 60 A3.6 kVA continuous, 10.8 kVA noncontinuous12.6 kVA at 75%Headroom is limited on 60 A single phase
ADU 100 A7.2 kVA continuous, 15.2 kVA noncontinuous20.4 kVA at 75%Fits 100 A only if demand assumptions hold
Three phase shop 125 A12 kVA continuous, 28 kVA noncontinuous36 kVA at 75%Three phase voltage basis lowers feeder amps
Continuous-load tip

Keep continuous loads in their own VA bucket. The calculator applies 125% only to that bucket, so a server rack or charger does not get blended into intermittent tool or receptacle demand.

Headroom tip

Use the smaller practical limit between the feeder breaker and the panel bus. A 100 A panel on a 60 A breaker still has a 60 A feeder limit for this planning check.

When you add a subpanel to a garage, a basement, or an accessory dwelling units, you have to make sure that the feeder can handle the electrical loads that will be added to that subpanel. The feeder itself must be large enough to handle all of the electrical loads, and it must be able to handle both continuous and noncontinuous loads. Many people makes the mistake of simply adding the nameplate numbers of all of the electrical devices that they plan to add to the subpanel.

However, adding these nameplate numbers together will give incorrect results because it does not take into account the difference between continuous and noncontinuous electrical load. For instance, if you are adding an electric vehicle charger and lights to the basement, the lights and electric vehicle charger may be running for extended period of time, and these loads could push the feeder beyond it’s capacity. An electrical load that is expected to run for three hour or more is referred to as a continuous load.

How to Size a Feeder for a Subpanel

Any continuous loads must be calculated at 125% of the actual Volt-Ampere (VA) value of the load prior to adding other electrical loads to the total. Electrical loads that are not expected to run for three hours or more is referred to as noncontinuous loads. You can apply demand factors to noncontinuous loads to account for the fact that they will not be running at maximum power simultaneously.

Thus, continuous and noncontinuous loads should be separated prior to performing any calculations regarding the electrical loads that will be added to the subpanel. In the example of the basement that is to be rewired with a subpanel, there may be recessed lights, a bath fan, and a heater in the basement. The lights and bath fan are examples of continuous loads, so you must multiply them by 1.25.

The electrical receptacles and shop tools in the basement are examples of noncontinuous loads, and those loads can be reduced via the application of a demand factor. For instance, if 75% is used as the demand factor for the tools in the shop instead of the 100% demand factor for all of the electrical loads, this will make a difference in whether a 60-amp or 80-amp breaker is needed for the basement subpanel. The breaker size is based off the calculated amperage of the electrical loads, not the total number of amps that the electrical devices will draw when they are operating.

The next size of breaker should be selected above the total calculated amperage; however, you must also compare the size of the breaker to the rating of the panel bus. For instance, if the panel bus is rated to handle 100 amps of electrical current, but the calculated amperage of the basement subpanel is 60 amps, a 60 amp breaker would be selected for the feeder. However, if the panel bus is only 60 amps, then the amperage of the feeder will be the limiting factor, and you should use a 60 amp breaker for that subpanel.

Thus, the feeder amperage must be compared to the panel bus amperage. Adding electrical loads to a subpanel after the initial calculation of the feeder can create electrical problems. For instance, if a basement subpanel is created that also includes receptacles for a dust collector and a 240-volt heater for the workshop, the power for these two receptacles are considered to be noncontinuous loads.

However, if the dust collector and the heater is expected to be operating at the same time, this could make the initial calculation based upon a demand factor incorrect. Thus, it is a recommendation to provide headroom for any future electrical loads in the subpanel to avoid having to rewire the entire subpanel. Three-phase electrical systems require different mathematical calculations than single-phase electrical systems due to the use of the square root of three in the denominator of the electrical load calculation formula.

Three-phase systems create less line current than single-phase systems if they contain the same total Volt-Amps (VA). Three-phase systems distribute the electrical load across three separate legs instead of the two legs of a single-phase electrical system. Thus, electrical calculations should include the type of electrical system that is to be created so that any calculations will automatically perform the necessary calculations to convert single phase electrical systems to three phase electrical systems (or vice versa).

Demand factors for electrical loads are percentages of the total calculated load. However, the percentage should represent the actual percentage of the electrical loads that will be used. For instance, people often apply a 75% demand factor to electrical loads in a garage.

However, a 75% demand factor assume that not all of the devices in the garage will be running at the same time. Thus, if the garage contains circuits for two different vacuum cleaners and each vacuum cleaner is expected to run constant, 75% may not be a realistic demand factor for the garage. A 100% demand factor could be used instead, though, since there is no evidence that the electrical equipment will not be running at the same time.

Finally, the limit of the panel bus must not be exceeded. The feeder and the breaker sizes may be calculated for a specific amount of amperage, but the electrical current that is created in the panels cannot exceed the panel bus rating. For instance, a main-lug subpanel may be rated at 125 amps, but it is impossible for that subpanel to exceed that 125 amp electrical current.

The electrical capacity of the feeder panel is the smaller of the two values (feeder breaker size and panel bus size). Thus, any calculations of amperage must be made certain to compare the calculated amperage to both the feeder breaker and the panel bus rating to ensure the electrical system is safe. In order to ensure that the feeder will not be the weak link in the electrical system, there are several steps that should be followed.

First, any continuous loads must be separated from the noncontinuous loads. Second, you must multiply the continuous loads by 1.25. Third, a demand factor should be selected that matches the use of the electrical equipment.

Finally, the calculated amperage should be compared to both the feeder breaker and the panel bus.

Sub Panel Load Calculator

Leave a Comment