Transformer Fuse Size Calculator: Find the Right Fuse Fast

⚡ Transformer Fuse Size Calculator

Calculate the correct primary & secondary fuse ratings based on NEC 450.3 for any transformer

🔌 Quick Presets
📋 Transformer Details
⚠ Please enter valid values for kVA, primary voltage, and secondary voltage.
✅ Fuse Size Calculation Results
📊 Standard Fuse Sizes Reference (Amps)
15A
Minimum
20A
Light Load
30A
Small Xfmr
60A
Mid-Range
100A
Large Xfmr
200A
Heavy Duty
400A
Industrial
600A
Max Standard
📐 Common Single-Phase Transformer Fuse Reference
kVA Rating Primary 120V Primary 240V Primary 480V Secondary 120V Secondary 240V
0.5 kVA6A → 15A3A → 15A2A → 15A5A → 15A3A → 15A
1 kVA10.4A → 15A5.2A → 15A2.6A → 15A8.3A → 15A4.2A → 15A
2 kVA20.8A → 30A10.4A → 15A5.2A → 15A16.7A → 20A8.3A → 15A
3 kVA31.3A → 40A15.6A → 20A7.8A → 15A25A → 30A12.5A → 15A
5 kVA52.1A → 70A26A → 30A13A → 15A41.7A → 50A20.8A → 25A
7.5 kVA78.1A → 100A39.1A → 50A19.5A → 25A62.5A → 80A31.3A → 40A
10 kVA104.2A → 125A52.1A → 60A26A → 30A83.3A → 100A41.7A → 50A
15 kVA156.3A → 200A78.1A → 100A39.1A → 50A125A → 150A62.5A → 80A
25 kVA260.4A → 300A130.2A → 150A65.1A → 80A208.3A → 250A104.2A → 125A
37.5 kVA390.6A → 400A195.3A → 200A97.7A → 110A312.5A → 350A156.3A → 175A
📐 Three-Phase Transformer Fuse Reference (480V Primary)
kVA Rating FLA Primary (A) 125% Primary Recommended Fuse FLA Secondary 208V Secondary Fuse
9 kVA10.8A13.5A15A25A30A
15 kVA18.0A22.5A25A41.6A50A
30 kVA36.1A45.1A50A83.3A100A
45 kVA54.1A67.6A70A124.9A150A
75 kVA90.2A112.8A125A208.2A225A
112.5 kVA135.3A169.1A175A312.3A350A
150 kVA180.4A225.5A250A416.4A450A
225 kVA270.6A338.2A350A624.5A700A
300 kVA360.8A451.0A500A832.7A900A
500 kVA601.4A751.7A800A1387.8A1600A
🧮 NEC 450.3 Maximum Overcurrent Protection
Location Impedance Primary Max % Secondary Max % Notes
Supervised (supervisory controlled)Any250%250%NEC 450.3(A)
Unsupervised – Primary Only< 6%125%NEC 450.3(B) Row 1
Unsupervised – Primary Only≥ 6%300%NEC 450.3(B) Row 2
Unsupervised – Both Sides< 6%250%125%NEC 450.3(B) Row 3
Unsupervised – Both Sides≥ 6%250%250%NEC 450.3(B) Row 4
🔍 Standard Fuse Size Chart (Next Standard Size Up)
Calculated Amps Next Standard Fuse Calculated Amps Next Standard Fuse
0 – 15A15A151 – 175A175A
16 – 20A20A176 – 200A200A
21 – 25A25A201 – 225A225A
26 – 30A30A226 – 250A250A
31 – 35A35A251 – 300A300A
36 – 40A40A301 – 350A350A
41 – 50A50A351 – 400A400A
51 – 60A60A401 – 450A450A
61 – 70A70A451 – 500A500A
71 – 80A80A501 – 600A600A
81 – 90A90A601 – 700A700A
91 – 100A100A701 – 800A800A
101 – 110A110A801 – 1000A1000A
111 – 125A125A1001 – 1200A1200A
126 – 150A150A1201 – 1600A1600A
💡 NEC 450.3 Rule: For unsupervised installations with impedance less than 6%, the primary overcurrent protection must not exceed 125% of the rated primary full-load current. Always round up to the next standard fuse size when the 125% calculation does not land on a standard size.
⚠ Safety Note: These calculations are based on NEC 450.3 guidelines. Always verify with your local Authority Having Jurisdiction (AHJ) and applicable local codes. A licensed electrician should verify all transformer protection designs before installation.

Election of the right fuse for a transformer seems simple, but it quickly becomes a difficult task. The main protective fuse must handle the strong inrush of current in a transformer that reaches up to 30 times the usual current for around 0.01 seconds. When the device first turns on, that sudden energy spike can destroy a fuse that is a bit too small.

The fuse usually is designed for 125 % of the maximum kVA of the transformer. For instance, a 45-kVA step-up transformer with 125-amp input requires a 156-amp fuse at 125 %, so one rounds it to standard 175-amp size. The section 450.3(B) of NEC shows the biggest fuse values and serves as an important guide for right choices.

How to Choose a Fuse for a Transformer

Sizes of circuit breaker and fuse follow NEC 450.3 together with the standard values from NEC 240.6(A).

Some installations apply up to 250 % rating. For a 10 000-kVA transformer in 480 volts three-phase, the computation uses the formula with 1,732 and later multipleis by 2,5.

In smaller transformers the calculations are easier. A 40-VA transformer with 24-volt secondary coil at 1.67 amps, a 2-amp fuse answers. In the basic side with 120 volts, the same device takes almost 0.33 amps, and the nearest standard fuse works.

Fourth sample: a 75-watt transformer in 120 volts uses 0.625 amps, so a 0.5-amp fuse forms a good start.

Cheaper transformers sometimes use some idle current, so plan for around 0.5 amps in the main input fuse is wise four units of lower quality.

For work with utilities and usual volts like 19.9 and 7.6, it is enough to recall only four fuse sizes for most tasks. A 25-kVA transformer at 19.9 requires a 3-amp fuse. A 50-kVA at 19.9 requires a 5-amp fuse.

At 7.6 volts, 25-kVA takes 10 amps while 50-kVA reaches 15 amps.

Fuses of CC-class have smoother curves than those of J- and RK-classes. CC-fuses come in sizes of around 0.2 to 30 amps. When one skips the secondary protection, the primary can be fused at 125 % of the primary current, then rounding to the next usual size.

Before, choices of fuses at makers of transformers meant line-to-line primary at 480 volts and line-to-neutral secondary at 120 volts. If the transformer is wired only for 120-volt output, even secondary fusing doesnotnecessarily need to be there.

A fuse mainly serves to protect the wires, so it is always chosen according to the ratings of the wires too.

Transformer Fuse Size Calculator: Find the Right Fuse Fast

Leave a Comment